INDUSTRY

Filtration of water networks

Industrial sites need quality water, either for process water or cooling network.

For process water, Hectron filters improve water quality, coming from rivers or borehole. Our filters are fully automatic, have no need of consumables and require minimum maintenance.

Cooling networks and cooling towers quickly load with dust, fine metal particles, plastic residues (in plastics factories) or algae. Compared to magnetic filters, our filters retain more solids, including non-metallic dust. Having a good filtration helps to reduce water chemical treatment.

Suitable equipment

AG AUTOMATIC FILTERS

Versatile filters, range available for flow rates up to 340 m3/h and operating pressure up to 16 Bar

Benefits

AS AUTOMATIC FILTERS

Models suitable for low-pressure networks: filling a buffer tank, cooling tower.

Benefits

References

La Mesta chimie fine, Gilette (France).

Filter in the treatment of a cooling tower. Bypass filtration: pump + AG300 316L filter (50 μm) + VSM pressure maintainer. Flow rate 50 m³/h.

Algerian Qatari Steel, El Milia, Algeria

Bellara steelworks. Filtration of the steelworks’ cooling network. Low-pressure network requiring fine filtration. Hectron supplied two AS400 DN150 6 μm filters (capacity of 100 m³/h each).

Conflandey, Port-sur-Saône (France)

Steel wire drawing plant. Machine cooling network with cooling tower. To limit the growth of flora clogging the pipes while reducing chemical water treatment, a filtration system was installed. From a total flow rate of 350 to 400 m3/h, a portion of the water (60 m³/h) is sampled and filtered through an AG300 DN100 with a 20 μm filter.

Johnson Controls Industrie / Thales, Thônon les Bains (France)

Filtration of the plant’s cooling network. AG400 DN250 with a 100 μm filter.

Fleury Michon, Chantonnay (France)

Filtration at the outlet of the plant’s WWTP. The existing filters (500 μm) did not provide sufficient water quality. Installation of an AG200 2” PN10 200 μm filter.

Automatisme Industrie / Mecaplast, Lens (62)

Treatment of effluent from the manufacturing of electronic equipment. After a biological process, final filtration of the water at the flotation tank outlet by an AG300 316L-E DN150 100 μm.